5069 Insulation Tester Calibrator

All about product
Specification
Reviews
0
Questions
0
Product Code: 5069
Reviews: 0
0.00€
Ex Tax: 0.00€
Specifications: (See all)
Additional options
Calibration certificates: Traceable (factory) and accredited (ISO 17025).
Fixed Values
5 MΩ, 2 MΩ, 1 MΩ, 500 kΩ, 200 kΩ, 100 kΩ
Open Circuit Voltage Measure
0 to 2 kV range, accuracy 1 % FS. 0 to 10 kV range, accuracy 2 % FS
Package contents
Safety connection leads with bare end to allow custom probes (10 kV rated), 4 mm 5 kV test lead set, pouch to carry test leads, and mains charger
Power supply
Internal battery, 6 V re-chargeable NiCad, > 150 hours between charges.
Description

A precision instrument suitable for calibrating and testing general purpose insulation testers and megohmmeters with test voltages up to 10 kV.

The 5069 is housed in a durable safety case and is powered by a rechargeable battery. This ensures full isolation from the mains and prevents stray leakage.

The insulation tester being calibrated can be tested for open circuit voltage and short circuit current. These are displayed on the digital meter mounted on the front panel. The insulation resistance is provided by a precision 4 dial decade resistance bank which can be set to a maximum of 99.99 GΩ with additional resistance values of 100 kΩ, 200 kΩ, 500 kΩ, 1 MΩ, 2 MΩ and 5 MΩ which can be switched in as required.

Rugged and portable, the 5069 is ideal for site calibration work. Also available is the 5068 Insulation Tester Calibrator, 2.5 kV version. For additional electrical testing capabilities the 5030 calibrator is a laboratory calibrator for multifunction installation testers.

Specifications
Main characteristics
Fixed Values
5 MΩ, 2 MΩ, 1 MΩ, 500 kΩ, 200 kΩ, 100 kΩ
Open Circuit Voltage Measure
0 to 2 kV range, accuracy 1 % FS. 0 to 10 kV range, accuracy 2 % FS
Resistance
10 GΩ, 1 GΩ, 100 MΩ, 10 MΩ decade ranges
Short Circuit Current Measure
0 to 2 mA range and 0 to 20 mA range = 1 % FS accuracy
Temperature Coefficient
Less than 250 ppm per °C
Voltage Display
1.999 kV full scale, and 10 kV full scale
Accuracy
100 kΩ to 5 MΩ = 1%. 10 MΩ to 10 GΩ = 1%. 10 GΩ to 100 GΩ = 5%
Autonomy
Power supply
Internal battery, 6 V re-chargeable NiCad, > 150 hours between charges.
Physical parameters
Size
W 406 x H 175 x D 330 mm
Weight
4.4 kg
Completeness
Additional options
Calibration certificates: Traceable (factory) and accredited (ISO 17025).
Package contents
Safety connection leads with bare end to allow custom probes (10 kV rated), 4 mm 5 kV test lead set, pouch to carry test leads, and mains charger
Reviews
0 / 5
average product rating
0
0
0
0
0

There are no reviews for this product, be the first to leave your review.

Answers & questions

No questions about this product, be the first and ask your question.

5069 Insulation Tester Calibrator
0.00€