Description

The extCZIP®-PV PRO relay is intended for switchgear operating at the connection points of photovoltaic plants to the MV or LV distribution networks, as well as for the micro-installations. The device meets all requirements regarding power system protection for PV plants, specified in the Grid Code of the Polish Distribution System Operators (IRiESD) and the PN-EN 50549-1 and PN-EN 50549-2 standards. It includes protections supplied from both MV and LV voltage circuits.
To perform the required functions, the new relay is equipped with additional inputs for voltage and current measurement at the LV side.

  • programmable logic support (50),
  • colour LCD TFT 7” screen, 800x480, with a touch panel,
  • bay synoptic diagram presentation with mapping of the switch states,
  • switch control from the synoptic screen and using telemechanics (up to 11 switches),
  • presentation of the recorded events, measurement values and input or output states,
  • 28 or 56 opto-isolated binary inputs,
  • 20 or 40 output relays,
  • 14 bi-colour programmable LEDs, with on-screen description,
  • ON and OFF buttons – to control the bay circuit breaker from the device keyboard,
  • 512 MB internal memory for recording samples of disturbance recorder, event recorder, energy measurements,
  • time synchronization via Ethernet network using SNTP,
  • independent communication interfaces: USB, 2 x RS-485, Ethernet 10/100 BASE-TX (optional fibre optic port and CAN-BUS/RS-485),
  • communication protocols: DNP 3.0, IEC 60870-5-103 and 104, IEC 61850, Modbus® ASCII / RTU (optional PPM2 protocol on CAN-BUS/RS-485 port),
  • 2-bit status monitoring of all switches,
  • optional phase current measurement inputs adapted for operation with low-power current transformers based on Rogowski coils.